systems

Systems

Developed with telecom backup in mind, these solutions provide a flexible backup power solution complete with DC-DC conversion and UPS switch all wrapped in a heavy duty outdoor enclosure.

 

Backup power systems

3kW system

Product O.D.
Outer dimensions (mm) 600 x 700 x 1,200 (L x W x H)
Weight (kg) 200
Operating conditions
Operating temperature (℃) 65
Ambient operating temperature (℃) Customer specified
Ambient operating humidity 0~90%
Ambient storage temperature (℃) -20~45, or customer specified
Ambient storage humidity 0~95%
Input requirements
Fuel H₂>99.99%
Oxidant O₂>99.9%
Coolant Deionized water
Output standard
DC voltage output (V) 43.2~57.6
Rated voltage output (V) 48
Maximum current (A) 50
Rated power output (W) 3,000

Development systems

3kW backup solution

3kW-System3kW-System (2)

Product O.D.
Outer dimensions (mm) 600 x 482.6 x 330 (L x W x H)
Weight (kg) 55
Operating conditions
Operating temperature (℃) <65
Ambient operating temperature (℃) Customer specified
Ambient operating humidity 0~90%
Ambient storage temperature (℃) -20~45, or customer specified
Ambient storage humidity 0~95%
Input requirements
Fuel H₂>99.99%
Oxidant O₂>99.9%
Coolant Deionized water
Output standard
DC voltage output (V) 20~36
Rated current output (A) 180
Rated power output (W) 3,500
Peak current (A) 270 (10 minutes sustained)
Continuous operation (h) >24
Life 10 years>1,000 start-ups